IIAR Set to Release Hydrocarbon Standard in 2027

After nearly eight years of development, IIAR’s hydrocarbon standard is set to be published in early 2027. The standard is the second comprehensive safety standard for a refrigerant other than ammonia, following the publication of IIAR’s CO2 standard in 2021.

Hydrocarbons have long been seen as one of the most promising natural refrigerant replacements for F-gases in commercial refrigeration systems. While they are already in wide use in commercial systems, concerns over flammability have traditionally kept their use limited in industrial applications.

However, as refrigerant options narrow due to new environmental concerns over PFAS contamination from hydrofluoroolefins, or HFO refrigerants, traditional concerns may no longer figure as prominently in refrigerant decisions. Especially when those concerns include how to apply the refrigerant safely, a factor that can be addressed with an IIAR safety standard.

Don Faust, IIAR’s Standards Committee Chair, said IIAR’s standard is meant, in part, to open the door to the wider industrial use of hydrocarbons by addressing safety through IIAR’s well established consensus process.

“I don’t think that the future of natural refrigerants will be a competition between ammonia, CO2 and hydrocarbons,” said Faust. “The future is going to be finding the right refrigerant for the right applications.”

In the case of hydrocarbons, those applications will grow when barriers like safety concerns are addressed. From that perspective, “it’s a chicken or egg situation. What comes first, development of the technology or industry adoption?” said Faust. He added that IIAR’s consensus process solves the adoption problem.

“IIAR has created a common framework that reflects the industry’s safety culture. The hydrocarbon standard is about providing a framework for safely adopting another natural refrigerant,” said Faust. “With ammonia and CO2, we addressed the toxicity and pressure hazards and now with hydrocarbons we’re addressing flammability.”

Many hydrocarbons make great refrigerants. They are natural, have zero ODP, a GWP less than four, and are categorized as nontoxic, said Bruce Nelson, former IIAR Board Chairman. “Hydrocarbons are compatible with copper and with many low-cost components, such as hermetic and semihermetic compressors, expansion valves, and heat exchangers used in the HVAC and commercial refrigeration industries.

Compatibility with standard compressor lubricants, desiccants, and elastomers is also excellent.”

“The hydrocarbons are already in wide use – for cooking, heating, transportation, and power generation. Based on these characteristics the hydrocarbons are the only natural refrigerants that can match or beat the F-gases in commercial refrigeration systems on the basis of first cost and energy efficiency,” said Nelson. “Given the above, one must ask: “Why are we not making more use of the hydrocarbons as refrigerants?”

The answer of course is flammability.” Faust said that foundation of safety is what lays the groundwork for the adoption of any new IIAR standard.

“We have the ability to create standards that reflect a great amount of industry knowledge through the commitment of volunteers who know how to write them.” The new hydrocarbon standard was especially complex because it was written to encompass all relevant fire code.

“A lot of us thought this would be a simple standard,” said IIAR’s Hydrocarbon Subcommittee Chair, Joe Pillis, adding that the standard turned out to be more complex than expected. “The more we researched how many codes in the U.S. we had to comply with, we realized it was not as straightforward,” he said.

Pillis said five major codes were considered: NFPA 1, the International Building Code, the International Fire Code, the International Mechanical Code and the Uniform Mechanical Code.

“There are many codes that already have language around hydrocarbons used as refrigerants. We wanted to write a standard that is compatible with all of these codes,” said Pillis. “It made [the standard] more of a difficult task because we have an extensive code foundation here. We went through all of the codes and generally picked the most stringent. That’s what ended up in the standard.”

The result was a 381-page “cradle to grave” standard that covers every aspect of safe use, from startup to maintenance to decommissioning. The standard has been through five public reviews over eight years and arrives just in time for the next major shift in regulation, the potential phase-out of HFO’s.

“The regulations out there that reduce the environmental impact have narrowed the number of possible refrigerants,” said Pillis. “Even if [HFO’s] get through all the GWP limits, they’re likely to have PFAS and TFA regulations to contend with next. People don’t want to face that HFO’s and A2Ls may be phased out because of the PFAS concerns.”

Pillis said that may be the thing that makes IIAR’s hydrocarbon standard especially relevant. “What’s left [in terms of usable refrigerants] are ammonia, CO2, and hydrocarbons. We have safety standards for ammonia and CO2, so we needed a standard for how to build safe hydrocarbon systems. And that’s what we built.”

The new standard has six parts, covering: design installation, start-up, inspection testing and maintenance, decommissioning, and general safety requirements. In addition to the basics, the standard addresses three areas that might be of particular interest to IIAR members. First, it specifies Class 1 Division 2 electricals regardless of whether a refrigeration system is installed in a machinery room or outdoors.

Second, there is no allowance in the standard for hydrocarbons to be used in a direct system to an occupied space. The standard specifies that there must be a secondary coolant.

The third area covers exhaust from the machinery room or from relief devices. “Exhaust from mechanical ventilation systems serving machinery rooms capable of exceeding 25 percent of the LFL or 50 percent of the Immediately Dangerous to Life or Health (IDLH) shall be equipped with approved treatment systems to reduce the discharge concentrations to those values or lower,” said Pillis. There are similar treatment requirements on a discharge from relief devices on any system with more than 6.6 pounds of refrigerant.

That requirement could force users to install a treatment system for relief valves and exhaust under the standard, such as absorption systems or flare, but also leaves some of the decision-making power with designers.

There is an exception in the standard that says: “The refrigerants may discharge directly to atmosphere outdoors if the authority having jurisdiction, or AHJ determines, upon review of an engineering analysis prepared at the expense of the owner, that a significant fire, health, or environmental hazard would not result from an atmospheric release. The analysis must be documented and retained on-site.”

“Systems may be able to discharge to atmosphere if an authority having jurisdiction, or AHJ, determines that [as an option] upon a review of an engineering analysis,” said Pillis. “That part of the standard allows a designer to have a consultant do an engineering analysis of their case. If the consultant says no environmental hazard exists, then they can discharge to atmosphere.”

Pillis said IIAR members should expect publication of the standard in 2027 following its IIAR Board of Directors November 2026 vote. He added that the standard may lay the groundwork for wider adoption of hydrocarbons, just as the question of whether or not to choose hydrocarbon systems becomes more relevant to the industry.

“I think that as refrigerant choices diminish hydrocarbons will be considered because they can be used in such a wide variety of applications, providing they can meet safety requirements. And now IIAR has a standard that shows users how to meet those requirements.”

The requirements laid out in IIAR’s hydrocarbon standard are specific to industrial and commercial refrigeration,” said Pillis.

“This is a tremendous resource because it represents the collective knowledge of our task group and ANSI’s consensus process. We have documented much of this specialized knowledge in one place with this new standard. It’s much more along the lines of the CO2 standard [as a comprehensive safety standard] than IIAR’s suite of standards for ammonia.”

Nelson agreed, saying, “IIAR is breaking new ground with this standard. We’ve done this to benefit our industry and accelerate the uptake of the use of all natural refrigerants.”